5-7            
5-2-5 Internal Torque Limit  
In torque Control mode, user can set internal torque limit values as required. Set as below: 
Parameter   Name  Default  Unit  Setting range  Control mode
Cn010 
CCW Torque 
command limit 
300 
/ 
200 
% 0~300  ALL 
Cn011 
CW Torque 
command limit 
-300 
/ 
-200 
% -300~0  ALL 
5-2-6 Limiting Servomotor Speed during Torque Control 
In torque control, input contacts SPD1 and SPD2 can be used for selecting one of the two 
methods below for setting speed limits.  
(1) External Analog command (Default) Signal is applied to terminals SIC & AG ( pins 
12 & 13 on CN1) 
(2)  Selection of Three presentable Limits (Tn105~Tn107) according to the table 
below. 
Caution! For achieving smooth speed response please refer to section 5-3-6. 
Input contact SPD2 
Input contact 
SPD1 
Speed limit command
Control 
mode 
0 0 
External analog 
command  
SIC(CN1-12)  
0 1 
Internal speed limit1 
Tn105 
1 0 
Internal speed limit2  
Tn106 
1 1 
Internal speed limit3  
Tn107 
T 
Note: Input contacts status “1”  (ON)  and  “0”  (OFF). 
Please check 5-6-1 to set the required high /Low signal levels ( PNP/NPN) selection. 
 
Below is the external analog speed limit command wiring diagram:  
CNI-12
Drive
SIC
AG
Analog Speed 
Limit Input
(0~10V)
CNI-13
 
Internal presentable speed limit parameters for torque control mode are listed below: 
These preset limits apply to both CW & CCW directions.  
Parameter   Name  Default  Unit  Setting range  Control mode
Tn105  Internal speed limit 1 100  rpm  0~3000  T 
Tn106  Internal speed limit 2 200  rpm  0~3000  T 
Tn107  Internal speed limit 3 300  rpm  0~3000  T 
 P.S also refer to page 6-11 for detail.