Comm5 wiring
BMTX-SVN01C-EN 47
Figure 24. Shield termination for existing sites using the Trane-
approved, purple-jacketed, shielded wire for Comm5 links
Figure Note:
Each link of the configuration that is created by the repeater requires termination resistors.
Shield wires entering the repeater should be connected to a terminal marked with a capacitor symbol. The entering shield wire must
be connected to earth ground at the BCU.
Shield wires leaving the repeater should be connected to the repeater terminal marked with an earth ground symbol.