Comm5 wiring
BMTX-SVN01C-EN 47
Figure 24. Shield termination for existing sites using the Trane-
approved, purple-jacketed, shielded wire for Comm5 links
Figure Note:
• Each link of the configuration that is created by the repeater requires termination resistors.
• Shield wires entering the repeater should be connected to a terminal marked with a capacitor symbol. The entering shield wire must
be connected to earth ground at the BCU.
• Shield wires leaving the repeater should be connected to the repeater terminal marked with an earth ground symbol.