Description of UCM types
BMTX-SVN01C-EN 87
77 on on OFF on on
78 on on on OFF OFF
79 on on on OFF on
80 on on on on OFF
81 on on on on on
Note:
SW1-1 is used to enable (switch on) or disable (switch off) the normally closed High
Temperature Limit Switch input (TB2 on the TCI-3 board).
Cycle power off/on after changing switch settings.
Table 24. Voyager rooftop unit UCM address settings (Continued)
UCM
address
TCI Board DIP switch settings
SW1-2 SW1-3 SW1-4 SW1-5 SW1-6