D301087 0308 - BL20 CANopen 4-141
I/O-Module Objects
4
BL20-2AI-PT/NI-2/3
Table 83:
Parameter data
BL20-2AI-PT/NI-
2/3
A default setting
Byte Bit Parameter Value/ Meaning
n0Mains
suppression
0 = 50 Hz
A
1 = 60 Hz
1Value
representation
0 = Integer (15 bit + sign)
A
1 = reserved
2 Diagnostic 0 = release
A
1 = block
3 Channel Kx 0 = activate
A
1= deactivate
4 to
7
Element 0000 = Pt100, -200...850 °C
A
0001 = Pt100, -200...150 °C
0010 = Ni100, -60...250 °C
0011 = Ni100, -60...150 °C
0100 = Pt200, -200...850 °C
0101 = Pt200, -200...150 °C
0110 = Pt500, -200...850 °C
0111 = Pt500, -200...150 °C
1000 = Pt1000, -200...850 °C
1001= Pt1000, -200...150 °C
1010 = Ni1000, -60...250 °C
1011 = Ni1000, -60...150 °C
1100 = Resistance, 0...100 Ω
1101 = Resistance, 0...200 Ω
1110 = Resistance, 0...400 Ω
1111 = Resistance, 0...1000 Ω
n +1 0 measurement
mode
0 = 2-wire
A
1 = 3-wire