BL20 - Communication in CANopen
D301087 0308 - BL20 CANopen4-142
BL20-2AI-THERMO-PI
Table 84:
Parameters
BL20-2AI-
THERMO-PI
A default setting
Byte Bit Parameter Value/ Meaning
n0Mains
suppression
0 = 50 Hz A
1 = 60 Hz
1Value
representation
0 = Integer (15 bit + sign)
A
1 = reserved
2 Diagnostic 0 = release
A
1 = block
3 Channel 0 = activate
A
1= deactivate
6 to
4
Element 0000 = type K, -270...1370 °C
A
0001 = type B, +100....1820 °C
0010 = type E, -270...1000 °C
0011 = type J, -210...1200 °C
0100 = type N, -270...1300 °C
0101 = type R, -50...1760 °C
0110 = type S, -50...1540 °C
0111 = type T, -270...400 °C
1000 = ±50 mV
1001 = ±100 mV
1010 = ±500 mV
1011 = ±1000 mV
7 reserved