D301087 0308 - BL20 CANopen 4-225
I/O-Module Objects
4
Object 5820
hex
- Measuring Integration Time
Object 5820
hex
is used to set the Integration time for measurement
mode. Permissible values are: 1 to 1000.
In Frequency measurement mode the module counts the pulses
that are received in the defined integration time and calculates an
average frequency from this. The value range for the integration time
can be set in 10 ms increments between 10 ms to 10000 ms.
In revolutions measurement mode the counter module counts the
pulses received from a rotary sensor within a predefined integration
time. The number of “sensor pulses per revolution” must be defined
beforehand by parameters in the system. The number of “sensor
pulses per revolution” and the pulses counted determines the speed
of the connected motor. The value range for the integration time can
be set in 10 ms increments between 10 ms to 10000 ms.
Sub-index 00
hex
Data type Unsigned8
Access ro
Default value No
Sub-index 01
hex
- 47
hex
Data type Unsigned16
Access rw
Default value No
Table 154:
Object 5811
hex
Feature Description