BL20 - Communication in CANopen
D301087 0308 - BL20 CANopen4-228
Object 5822
hex
- Measuring High Limit
Object 5822
hex
is used to set the upper measuring limit for the BL20
counter module.
Permissible value range: 1 to 16777215
Write accesses initiate a parameter update on the BL20 internal
module bus.
The parameter is stored retentively in the gateway and is restored
with every node reset.
Note
The object 5822
hex
is only valid if the counter module is operating in
measurement mode.
Table 157:
Object 5822
hex
Feature Description
Name Measuring High Limit
Object code ARRAY
PDO-mapping No
Sub-index 00
hex
Data type Unsigned8
Access ro
Default value No
Sub-index 01
hex
- 47
hex
Data type Unsigned32
Access rw
Default value No