EasyManua.ls Logo

turck BL20 - Page 315

turck BL20
461 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D301087 0308 - BL20 CANopen 4-243
I/O-Module Objects
4
Object 6C01
hex
- Work Area Low Limit
Object 6C01
hex
(corresponds to object 6401
hex
in accordance with
CiA DS-406) defines the value for the lower count limit. In the event
of an underflow, bit 2 in object 6C00
hex
and bit 6 in object 5803
hex
are set.
The permissible range for the lower count limit is therefore:
-2147483648 to 0 (
hex
adecimal: 8000 0000
hex
to 0
hex
)
Note
The object 6C01
hex
is only valid if the counter module is operating in
count mode.
Table 172:
Object 6C01
hex
Feature Description
Name Work Area Low Limit
Object code ARRAY
PDO-mapping No
Sub-index 00
hex
Data type Unsigned8
Access ro
Default value No
Sub-index 01
hex
- 47
hex
Data type Unsigned32
Access rw
Default value No

Table of Contents