EasyManua.ls Logo

Tynetec Advent xt - Rs232 Ports; Network Termination Board; Link Settings; Inputs

Tynetec Advent xt
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DocNo.FM0410issueM1Page10
6.NETWORKTERMINATIONBOARD
TheAdventxtterminationboardprovidestheinterfacebetweenthemainCPUboardandthesitewiringnetwork.
RS232LINK16INPUTS XT ALTERA
PORT2SETTINGSOUTPUTSFUSES NETWORK NETWORK
     
JP2NETWORK1
RIBBONTO
CPUBOARD
NETWORK2
NETWORK3
RS232
PORT1
   
SMPSUINPUTSEXTPSUINPUTS AUDIOINPUTPA&D/EI/PLINK7
RS232 PORTS
Thestandard9pin“D”RS232port1isusedtoconnectalaptopPCtomonitorthenetworkcommsusingWindowsHyper
Terminal(19200baud,8databits,1stopbit,noparity).ThesecondRS232port2(MMJdatasocket)isusedtoconnecta
Tynetecinterface(P/No.ZXT295)toprogramnetworkdevicesincircuit(thisisprovidedwithaWindowsutilitywhichcan
alsobeusedtomonitornetworkcomms).ThecorrectlinksettingsLK1LK6mustbeselecteddependingonwhattheRS232
portisbeingusedfor.
LINK SETTINGS
LinksLK1toLK6willnormallybefittedasshownonthe drawingabove.ThesesettingsalloweitherRS232porttobeused
tomonitortheAdventxtnetworkdataviaWindowsHyperTerminalortheTynetecinterface.IftheRS232port2(MMJ
datasocket)isbeingusedtoprogramnetworkdevicesthenthelinksettingsmustbechangedasbelow.Link7hasno
currentfunction‐leavefittedinpositionA.
RS232PortMode LinkSettings
MonitorAdventxtComms LK1A LK2A LK3B LK4B LK5B LK6B
MonitorAlteraComms LK1B LK2B LK3B LK4B LK5B LK6B
ProgramAdventxtNetwork LK1A LK2A LK3A LK4A LK5B LK6B
ProgramAlteraI/OUnits LK1B LK2B LK3B LK4B LK5A LK6A

INPUTS
Thereare4inputswhichcanbeactivatedbyswitching0VvianormallyopencleancontactsintoterminalsIP1IP4.
InputNo. Function
IP1 Spare
IP2 Spare
IP3 Spare
IP4 FireAlarmTone
The“Brigadeoutput”relayonthebuilding’sFireAlarmPanelcanbeconnectedtoinput4toreportfirealarmsviathe
Adventxtsystem.