DocNo.FM0410issueM‐1Page4
2.SYSTEMOVERVIEW
PartNo. Description Notes
ZXT100 AdventxtController incbatterystandby&telecomdialler
ZXT122 AdventxtEthernetInterface(MK3) storesTelecaredataforremoteanalysis
ZXT155 PAAmplifier&SMPSU typically80PAintercomsperPSU
ZXT201 StandardIntercom
maximum255intercoms/callpointspersystem
ZXT206 StandardIntercom+PA
ZXT211 ExtracareIntercom
ZXT216 ExtracareIntercom+PA
ZXT280‐87 CombinedIntercomRange
ZXT250 ManagerCallpoint
ZXT260/5 LiftCallpoint(FlushS/S)
ZXT271 LiftCallpoint(SurfaceABS)
ZXT221 RemoteIntercom
1perintercom
ZXT226 RemoteIntercom+PA
S00600 CeilingPullcord maximum5perintercom(withLED)
N/A SmokeDetector
usemainspowereddetectorswithintegral
standbybattery&normallyopenrelayoutput
N/A PIRMovementDetector
use12VDCPIR’swithnormallyclosedrelay
output(additionalPSUmayberequired)
ZXT300 StatusModule 1persystem
ZXT311 MiniatureThermalPrinter 1perStatusModule
ZXT315 ManagersDisplayPanel 1persystem
ZXT325 169MHzNetworkReceiver
Total16persystem(maximum12zoned)
ZXT326 169MHzZonedNetworkReceiver
W06250 169MHzAerial&5mCoax 1perNetworkReceiver
ZXT4XX 169MHzRadioDevices maximum2048persystem
ZSD411 SiDigitalDoorPanel maximum16persystem
ZFT220 AdventxtTelephone 1perintercom
ZFT221 AdventxtDual Telephone slavetelephoneforabove
W00525 12V/2APowerSupplyUnit 1perDoorPanel(forlocksupply)
ZCS766 DeskTelephone maximum4persystem
ZXT556 MatrixIPPBX 1persite
ZXT503 Kirk400WirelessServer(SoloBase) 1persite(max6Repeaters)
ZXT504 Kirk400WirelessServer(MultiCell) 1persite(max3basestations/12repeaters)
ZXT536 IP12ChannelBaseStation maximum3persite(withMultiCellServer)
ZXT502 PoEInjector 1persite(SoloBase)
ZXT549 16PortFastswitch(8xPoE) 1persite(MultiCell)
ZXT512 2ChannelMultiCellRepeater max6perBase(Solo)or3perBase(MultiCell)
ZXT523/524 Spectralink7202/7212DECTHandset maximum12persite
ZCS729 KirkRepeaterProgrammingKit 1offpurchase
W00525 12V/2APowerSupplyUnit asrequiredforRepeaters
ZXT548 700VAUPS 1persiteforMatrixIPPBX&PoE/Fastswitch
ZXT330 BTLineSelectorUnit optional1persystem
ZXT130 DigitalCommuni cator optional1persystem
WIRING REQUIREMENTS
Onnewinstallationsthesystemwiringnetworkshouldbea6pairCW1308BTspeccable,onsiteswithexistingcablinga
minimumof5twistedpairsarerequired(or4pairswithoutPAordoorentry).
Thetelephonewiringnetworkshouldbea2pairCW1308BTspeccablewithBTmastersockets.AdedicatedPSTNlineis
requiredifthefacilitytoreportcallstoaremoteControlCentreisspecified.
A4pairCat5ecable(maxdistance100metres)isrequiredbetweenthePoEinjector/Fastswitch andtheKirk400Wireless
Server/IPBaseStations.RJ45wallsocketsandpatchleadsarerequiredtoterminatetheCat5ecable.
SYSTEM PROGRAMMING
ALaptopPCwithWindows98,2000orXPlnternetExplorerandaserialdatacableisrequiredforallsystemprogramming.
Windows7LaptopscanbeusedwithaMicroSoftapplicationthatrunsXPmode(onlycompatiblewithWindows7
Professional,EnterpriseorUltimateeditions).SeetheAdventxtProgrammingManual(TynetecDocNo.FM0411).