UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 39
Revision 7/06.12 of 63
Use function Calibration to “accelerate/
delay” the clock. Each entered positive unit
(“+”) accelerates the clock at the rate of 10,7s
per month; each negative unit delays the
clock at the rate of 5,35s per month.
The maximum rate is е +5,5min per
month or -2,75min per month.
12.4.5.3. Fire Alarm Lines in Test
Use this menu to set each of the three
fire alarming lines in Test Mode or to exit that
mode.
Upon selection of Test FA Lines, a
subordinate menu is entered:
- Test Line 1
- Test Line 2
- Test Line 3
Use the buttons and to choose
the line to be set to test mode and confirm
with button
The displayed screen provides the
option for alternating change of the parameter
Test “ON/OFF”. If it is “ON”, then the
respective line is set to test Mode. Use the
buttons Up and Down for the change.
Confirm the change of the parameter with
button .
A text message “Saved” appears for the
stored change.
The status of the line on the fourth line in
the display is changed to Tes.
For exit use button
12.4.5.4. Disables
The menu serves to disable/enable the
entered disable of fire alarm lines and some
outputs of the fire extinguishing control panel.
It contains the following functions:
Disable Line 1
Disable Line 2
Disable Line 3
Disable Rel 1ST
Disable Rel 2ST
Disable Output S1