Configuration and Programming
P/N 06-237041-001 3-11 February 2011
FOOTNOTES (Figure 3-13):
1 Isolated Devices. Purpose: To view the list of isolated devices and output circuits.
2 All System Events. List the Entire Contents of the System Event Log. Purpose: To view the
history of system events.
3 Range of Events. List the Contents of the System Event Log by Dates. Purpose: To view the
history of system events by selected dates.
4 SLC Test Results. List the Most Recent Test Results for the Initiating Devices on the SLC.
Purpose: To view the most-recent test results for the initiating devices on the SLC. These tests confirm
the abilities of the initiating devices to create and transmit alarm signals that can be properly interpreted
and processed by the FenwalNET 8000-ML control unit.
5 Walk Test Results. List Most Recent WalkTest Results for the Initiating Devices on the SLC.
Purpose: To view the most-recent walk-test results for the initiating devices on the SLC.
6 Device Readings. List a Range of Automatic Detector Sensitivity Settings. Purpose: To view
the pre-alarm and alarm thresholds for a range of automatic detectors and to view the fire
signatures being currently measured by the detectors. This procedure fulfills the intent of NFPA
72 (2002) Paragraph 10.4.3.2.4, Part (4) as a test to ensure that each smoke detector is within
its listed and marked sensitivity range.