Configuration and Programming
February 2011 3-40 P/N 06-237041-001
Any initiating devices not selected for walk testing will report events as normal. Any alarm reported
during a walk test will end the walk-test mode and cause the alarm report to be processed..
3 Silent Walk Test. Run a Silent Walk Test.
Purpose: To suspend normal system operation for functional testing of one or more SmartOne
initiating devices.
The FenwalNET 8000-ML control unit will operate identically as in standard Walk Test mode when
in a silent Walk Test mode, except that it will not energize the outputs programmed for walk-test
activation.
4 Stop Walk Test. End Walk Test. Purpose: To terminate a walk test.
Note: The walk-test mode will automatically end after 30 minutes of inactivity. It can also be
stopped by a system reset.
5 Alarm Sim Test. Run an Alarm-Simulation Test. Purpose:
Purpose: To activate system outputs by simulating an initiating-device event during system testing.
The initiating device is not activated. The FenwalNET 8000-ML system outputs are activated as if the
simulated initiating device had actually reported an alarm condition.
The simulated alarm report causes execution of the control unit's application program and activates
any outputs in the general-alarm list. Event acknowledgment, alarms silencing, and a system reset
are required to return the system to normal operating condition.
Note: The simulated alarm report must be manually de-activated via a menu operation before the
system can be reset and returned to normal operating condition.
The alarm-simulation test can be run concurrently for multiple devices to test counting and crossed-zoned
applications. Subsequent alarm acknowledgment and silencing are required. Each simulated initiating
device must be manually de-activated via the menu before the control unit can be reset.
5 Alarm Sim Test. De-Activate an Alarm-Simulation Test.
Purpose: To report an "alarm-off" message from an initiating device whose activation was simulated.
CAUTION
Physically disconnect the wiring to all agent-release and pre-action-sprinkler circuits
before walk testing any SLC initiating devices. Restore the system to normal operating
condition at the conclusion of these tests and any other functional tests that were
performed.
CAUTION
Physically disconnect the wiring to all agent-release and pre-action-sprinkler circuits
before walk testing any SLC initiating devices. Restore the system to normal operating
condition at the conclusion of these tests and any other functional tests that were
performed.
CAUTION
Isolate all releasing outputs using the Isolate function and physically disconnect the wiring to
all agent-release, pre-action-sprinkler and auxiliary control circuits before running any alarm-
simulation test(s). Restore the system to normal operating condition at the conclusion of these
tests and any other functional tests that were performed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security FenwalNET 8000-ML and is the answer not in the manual?

UTC Fire and Security FenwalNET 8000-ML Specifications

General IconGeneral
BrandUTC Fire and Security
ModelFenwalNET 8000-ML
CategoryControl Unit
LanguageEnglish