Troubleshooting
February 2011 6-14 P/N 06-237041-001
L#: Addr
TYPE ERROR On
Device
Type
The device at address L#: Addr is
reporting a device type that is different
from the type of device that is
configured for that address
• Ensure that the device installed at
address L#: Addr matches the device
type configured for that address.
Install corrected device or correct
configuration file and re-upload
application.
• Use Handheld Programmer to test the
device if the device type matches the
entry in the configuration file. Replace
the device if it fails the test or if the
error message returns when the
device is re-installed.
• Intermittent type errors could be a
symptom of SLC wiring problems.
Check SLC wiring if random errors
are reported. Refer to Section 2-8.5.
Ensure that wiring-resistance and -
capacitance limitations have not been
exceeded.
L#: Addr
SWITCH INPUT ACTIVE On The contacts of AI device at address
L#: Addr are still connected. This fault
reports when AI is configured for switch
type inputs – Drill, Silence,
Acknowledge, etc. are left active.
• Disconnect the switch connected to
the AI device
• Check device to be sure the switch is
properly wired
L#: Addr
FAILED TO CARRY OUT
COMMAND On
An SLC output device at address
L#: Addr failed to process the activation
command.
• Check device connections to SLC
wiring
• Ensure that device has not been
removed
• Check SLC wiring for excessive
capacitance and/or resistance if the
device LED is blinking. Refer to
Section 2-8.5. Rewire SLC using
recommended wire in Appendix B.
• Perform a test to activate the device.
• Replace the device if above
procedures are unsuccessful.
L#: Addr
DETECTOR TBL On
AnaLASER Interface Module
A problem in a high-sensitivity smoke
detector (HSSD) being monitored by an
AIM/APIC
• Check the AIM/APIC-to-HSSD
connections
• Use LaserNET or AIR-Intelligence
Remote Configuration Software to
troubleshoot the HSSD.
• Refer to AnaLASER II Installation,
Operation, and Maintenance Manual,
P/N 89.200 or appropriate AIR-
Intelligence detector manual,
P/N 33-308100-001/-002/-003.
Table 6-2. SLC Events (Continued)
SLC Events
For the following SLC-related events, L# is the SLC loop number and Addr is the
device address.
Error Message Probable Cause Corrective Action