EasyManua.ls Logo

UTC Fire and Security FenwalNET 8000-ML - Table C-2. Releasing Devices - Solenoid-Based

UTC Fire and Security FenwalNET 8000-ML
242 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Agency Listed Compatible Devices
February 2011 C-2 P/N 06-237041-001
Table C-2. Releasing Devices - Solenoid-Based
Wire Length (ft.)
Device Model and
Part Number
I
(Max.)
Amps
Resistance
(Min.)
Ohms
“On” Time
12
AWG
14
AWG
16
AWG
18
AWG
Max.
No.
p e r
R-NAC
Circuit
Max.
No
per
RRM
Agency
Kidde-Fenwal
Sol. Model 890181
P/N WK-890181-000
2.40 10.0 Momentary 300 200 120 1 1 or 2 UL, FM
Kidde-Fenwal
Sol. Model 895630
P/N 81-895630-000
2.00 12.0 Momentary 300 200 120 1 1 or 2 UL, FM
Kidde-Fenwal
Model CXV Control
Unit
P/N 93-487100-001*
(using optional
Solenoid P/N
83-100034-001)
2.00 12.0 Momentary 360 240 140 1 1 or 2 UL, FM
Kidde-Fenwal
Sol. Model 486500-01
P/N 82-486500-010
0.240 103.0 Steady 3000 2000 1200 800 1 1 or 2 UL, FM
Kidde-Fenwal
Sol. P/N
06-118384-001
0.520 46.0 Steady 1440 760 480 340 1 1 or 2 UL
Kidde-Fenwal
Sol. P/N
38-509834-001
0.632 38.0 Steady 1050 550 330 240 1 1 or 2 ULC, FM
Kidde-Fenwal
Sol. P/N
38-509837-001
0.400 60.0 Steady 2300 1460 915 570 1 1 or 2 ULC, FM
Kidde-Fenwal
Sol. P/N
81-100000-001
0.440 59.0 Steady 2300 1460 915 570 1 1 or 2 UL, FM
Kidde-Fenwal Electric
Control Head
Model 897494
P/Ns 897494-000 and
WK-897494-000
1.50 15.9 Steady 380 240 150 1 1 UL, FM
Kidde-Fenwal Electric
Control Head
Model 897494
P/Ns 897494-530 and
WK-897494-530
1.50 15.9 Steady 380 240 150 1 1 UL, FM

Table of Contents