EasyManua.ls Logo

Vacon 100X series - Group 3.21: Pump Control

Vacon 100X series
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters vacon • 112
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.17 Group 3.21: Pump Control
6.1.17.1 Group 3.21.1: Auto-Cleaning
The Auto-cleaning function is used to remove any dirt or other material that may have attached
to the pump impeller. Auto-cleaning is used e.g. in wastewater systems to keep up the perfor-
mance of the pump. Auto Cleaning function can also be used to clear the blocked pipe or valve.
Table 105. Auto-cleaning parameters
Code Parameter Min Max Unit Default ID Description
P3.21.1.1 Clean Function 0 1 0 1714
0=Disabled
1=Enabled
P3.21.1.2 Clean Activation
DigIN
Slot0.1
1715
Digital input signal used to
start the Auto Cleaning
sequence.
Auto-cleaning sequence will
be aborted if activation sig-
nal is removed before the
sequence has been com-
pleted.
NOTE: The drive will start
if the input is activated!
P3.21.1.3 Clean Cycles 1 100 5 1716
Number of forward/reverse
cleaning cycles.
P3.21.1.4 Clean Forward Freq. 0.00 50.00 Hz 45.00 1717
Forward direction frequency
in Auto-cleaning cycle.
P3.21.1.5 Clean Forward Time 0.00 320.00 s 2.00 1718
Running time for forward
direction frequency in Auto-
cleaning cycle.
P3.21.1.6 Clean Reverse Freq. 0.00 50.00 Hz 45.00 1719
Reverse direction frequency
in Auto-cleaning cycle.
P3.21.1.7 Clean Reverse Time 0.00 320.00 s 0.00 1720
Running time for reverse
direction frequency in Auto-
cleaning cycle
P3.21.1.8 Clean Accel Time 0.1 300.0 s 0.1 1721
Motor acceleration time
when Auto-cleaning is active
P3.21.1.9 Clean Decel Time 0.1 300.0 s 0.1 1722
Motor deceleration time
when Auto-cleaning is active

Table of Contents