vacon • 79 Parameters
6
6.1.6 Group 3.5: I/O Config
6.1.6.1 Default assignments of programmable inputs
Table 58 below presents the default assignments of programmable digital and analogue inputs
in Vacon 100 X Solar Pump application.
6.1.6.2 Group 3.5.1: Digital inputs
Digital inputs are very flexible to use. Parameters are functions that are connected to the re-
quired digital input terminal (see chapter 4). The digital inputs are represented as, for example,
DigIN Slot A.2, meaning the second input on slot A.
It is also possible to connect the digital inputs to time channels which are also represented as
terminals.
NOTE! The statuses of digital inputs and the digital output can be monitored in the Multimo-
nitoring view.
Table 58. Default assignments of inputs
Input Terminal(s) Reference Assigned function Parameter code
DI1 8 A.1 Ctrl signal 1 A P3.5.1.1
DI2 9 A.2 Ctrl signal 2 A P3.5.1.2
DI3 10 A.3 External fault close P3.5.1.11
DI4 14 A.4 Preset frequency selection 0 P3.5.1.21
DI5 15 A.5 Preset frequency selection 1 P3.5.1.22
DI6 16 A.6 External fault close P3.5.1.13
AI1 2/3 A.1 AI1 signal selection P3.5.2.1.1
AI2 4/5 A.2 AI2 signal selection P3.5.2.2.1
Table 59. Digital input settings
Code Parameter Default ID Description
P3.5.1.1 Ctrl signal 1 A DigIN SlotA.1 403 Ctrl signal 1 when control place is I/O A (FWD)
P3.5.1.2 Ctrl signal 2 A DigIN SlotA.2 404 Ctrl signal 2 when control place is I/O A (REV)
P3.5.1.4 Ctrl signal 1 B DigIN Slot0.1 423 Start signal 1 when control place is I/O B
P3.5.1.5 Ctrl signal 2 B DigIN Slot0.1 424 Start signal 2 when control place is I/O B
P3.5.1.7 I/O B Ctrl Force DigIN Slot0.1 425 TRUE = Force the control place to I/O B
P3.5.1.8 I/O B Ref Force DigIN Slot0.1 343
TRUE = Used frequency reference is specified
by I/O reference B parameter (P3.3.1.6).
P3.5.1.9 Fieldbus Ctrl Force DigIN Slot0.1 411 Force control to fieldbus
P3.5.1.10 Keypad Ctrl Force DigIN Slot0.1 410 Force control to keypad
P3.5.1.11 Ext Fault Close DigIN SlotA.3 405
FALSE = OK
TRUE = External fault
P3.5.1.12 Ext Fault Open DigIN Slot0.2 406
FALSE = External fault
TRUE = OK
P3.5.1.13 Fault Reset Close DigIN SlotA.6 414 Resets all active faults when TRUE
P3.5.1.14 Fault Reset Open DigIN Slot0.1 213 Resets all active faults when FALSE