vacon • 135 Parameters
6
6.2.12 Analog outputs
P3.5.4.1.1 AO1
FUNCTION
This parameter defines the content of the analogue output signal 1. The scaling of the analogue
output signal depends on the selected signal. See Table 124.
54 No function
55 No function
56
Auto-cleaning active
Pump auto-cleaning function is activated.
57
Motor Switch Open
58
TEST (Always Closed)
59
No function
Table 124. AO1 signal scaling
Selection Selection name Description
0 Test 0% (Not used) Analogue output is forced either to 0% or 20% depending
on parameter P3.5.4.1.3.
1 TEST 100% Analogue output is forced to 100% signal (10V / 20mA).
2 Output frequency Actual output frequency from zero to MaxFreqReference.
3 Frequency reference Actual frequency reference from zero to MaxFreqRefer-
ence.
4 Motor speed Actual motor speed from zero to Motor Nom Speed.
5 Output current Drive output current from zero to Motor Nom Currnt.
6 Motor torque Actual motor torque from zero to motor nominal torque
(100%).
7 Motor power Actual motor power from zero to Motor Nom Power
(100%).
8 Motor voltage Actual motor voltage from zero to Motor Nom Voltg.
9 DC-link voltage Actual DC-link voltage 0…1000V.
10 PID output PID controller output (0…100%).
11 ExtPID output External PID controller output (0…100%).
12 Fieldbus Process Data In 1 Fieldbus Process Data In 1 from 0…10000 (corresponding
0…100.00%).
13 Fieldbus Process Data In 2 Fieldbus Process Data In 2 from 0…10000 (corresponding
0…100.00%).
14 Fieldbus Process Data In 3 Fieldbus Process Data In 3 from 0…10000 (corresponding
0…100.00%).
15 Fieldbus Process Data In 4 Fieldbus Process Data In 4 from 0…10000 (corresponding
0…100.00%).
16 Fieldbus Process Data In 5 Fieldbus Process Data In 5 from 0…10000 (corresponding
0…100.00%).
17 Fieldbus Process Data In 6 Fieldbus Process Data In 6 from 0…10000 (corresponding
0…100.00%).
Table 123. Output signals via RO1
Selection Selection name Description