6.1.8 Group 3.7: Prohibit Freq
In some systems it may be necessary to avoid certain frequencies due to mechanical reso-
nance problems. By setting up prohibit frequencies it is possible to skip these ranges. When
the (input) frequency reference is increased, the internal frequency reference is kept at the low
limit until the (input) reference is above the high limit.
6.1.9 Group 3.8: Supervisions
Choose here:
1. one or two (P3.8.1/P3.8.5) signal values for supervision.
2. whether the low or high limits are supervised (P3.8.2/P3.8.6)
3. the actual limit values (P3.8.3/P3.8.7).
4. the hystereses for the set limit values (P3.8.4/P3.8.8).
Table 70. Prohibit frequencies
Code Parameter Min Max Unit Default ID Description
P3.7.1 Range 1 Low Lim -1,00 320,00 Hz 0,00 509 0 = Not used
P3.7.2 Range 1 High Lim 0,00 320,00 Hz 0,00 510 0 = Not used
P3.7.3 Range 2 Low Lim 0,00 320,00 Hz 0,00 511 0 = Not used
P3.7.4 Range 2 High Lim 0,00 320,00 Hz 0,00 512 0 = Not used
P3.7.5 Range 3 Low Lim 0,00 320,00 Hz 0,00 513 0 = Not used
P3.7.6 Range 3 High Lim 0,00 320,00 Hz 0,00 514 0 = Not used
P3.7.7 Ramp TimeFactor 0,1 10,0 Times 1,0 518
Multiplier of the currently
selected ramp time between
prohibit frequency limits.
Table 71. Supervision settings
Code Parameter Min Max Unit Default ID Description
P3.8.1 Superv1 Item 0 11 0 1431
0 = Output frequency
1 = Frequency reference
2 = Motor current
3 = Motor torque
4 = Motor power
5 = DC-link voltage
6 = Analogue input 1
7 = Analogue input 2
8 = Analogue input 3
9 = Analogue input 4
10 = Analogue input 5
11 = Analogue input 6
P3.8.2 Superv1 Mode 0 2 0 1432
0 = Not used
1 = Low limit supervision
(output active under limit)
2 = High limit supervision
(output active over limit)
P3.8.3 Superv1 Limit -50.00 50.00 Varies 25.00 1433
Supervision limit for selected
item. Unit appears automati-
cally.
P3.8.4 Superv1 Hyst 0.00 50.00 Varies 5.00 1434
Supervision limit hysteresis
for selected item. Unit is set
automatically.
P3.8.5 Superv2 Item 0 11 1 1435 See P3.8.1