vacon • 85 Parameters
6
6.1.6.7 Expander slots D to E analogue outputs
Shows only parameters for existing outputs on option boards placed in slots D and E. Selec-
tions as in Standard AO1 (P3.5.4.1.1).
This group or these parameters are not visible if no digital outputs exist in slots D or E.
6.1.7 Group 3.6: Fieldbus DataMap
Fieldbus process data out
Default values for Process Data Out to monitor through fieldbus are listed in Table 69.
Example: Value ‘2500’ for
Output Frequency corresponds to ‘25.00 Hz’ (scaling value is 0.01).
All monitoring values listed in chapter 5 are given the scaling value.
Table 68. Fieldbus data mapping
Code Parameter Min Max Unit Default ID Description
P3.6.1 FB DataOut 1 Sel 0 35000 1 852
Data sent to fieldbus can be
chosen with parameter and
monitor value ID numbers.
The data is scaled to unsigned
16-bit format according to the
format on keypad. E.g. 25.5 on
keypad equals 255.
P3.6.2 FB DataOut 2 Sel 0 35000 2 853
Select Process Data Out with
parameter ID
P3.6.3 FB DataOut 3 Sel 0 35000 3 854
Select Process Data Out with
parameter ID
P3.6.4 FB DataOut 4 Sel 0 35000 4 855
Select Process Data Out with
parameter ID
P3.6.5 FB DataOut 5 Sel 0 35000 5 856
Select Process Data Out with
parameter ID
P3.6.6 FB DataOut 6 Sel 0 35000 6 857
Select Process Data Out with
parameter ID
P3.6.7 FB DataOut 7 Sel 0 35000 7 858
Select Process Data Out with
parameter ID
P3.6.8 FB DataOut 8 Sel 0 35000 37 859
Select Process Data Out with
parameter ID
Table 69. Fieldbus Process Data Out
Data Value Scale
Process Data Out 1 Output frequency 0.01 Hz
Process Data Out 2 Motor speed 1 rpm
Process Data Out 3 Motor current 0.1 A
Process Data Out 4 Motor torque 0.1 %
Process Data Out 5 Motor power 0.1 %
Process Data Out 6 Motor voltage 0.1 V
Process Data Out 7 DC-link voltage 1 V
Process Data Out 8 Last active fault code 1