vacon • 143 Parameters
6
6.2.16 Feedbacks
P3.13.1.9 D
EAD BAND
P3.13.1.10 DEAD BAND DELAY
The PID controller output is locked if the actual value stays within the deadband area around
the reference for a predefined time. This function will prevent unnecessary movement and
wear on actuators, e.g. valves.
Figure 50. Dead band
9097.emf
Dead band (ID1056)
Reference
Dead band delay (ID1057)
Output locked
Actual value