Parameters vacon • 74
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.4 Group 3.3: References
6.1.4.1 Frequency reference
The requency reference source is programmable for all control places except PC, which al-
ways takes the reference from the PC tool.
Remote control place (I/O A): The source of frequency reference can be selected with param-
eter P3.3.1.5.
Remote control place (I/O B): The source of frequency reference can be selected with param-
eter P3.3.1.6.
Local control place (Keypad): If the default selection for parameter P3.3.1.7 is used the refer-
ence set with parameter P3.3.1.8 applies.
Remote control place (Fieldbus): The frequency reference comes from fieldbus if the default
value for parameter P3.3.1.10 is kept.
Table 51. Frequency reference parameters
Code Parameter Min Max Unit Default ID Description
P3.3.1.1 MinFreqReference 0.00 P3.3.1.2 Hz 0.00 101
Minimum allowed frequency
reference
P3.3.1.2 MaxFreqReference P3.3.1.1 320.00 Hz 50.00 102
Maximum allowed frequency
reference
P3.3.1.3 PosFreqRefLimit -320.0 320.0 Hz 320.00 1285
Final frequency reference
limit for positive direction.
P3.3.1.4 NegFreqRefLimit -320.0 320.0 Hz -320.00 1286
Final frequency reference
limit for negative direction.
NOTE: This parameter can
be used e.g. to prevent motor
from running in reverse
direction.
P3.3.1.5 I/O A Ref sel 1 9 5 117
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P3.3.1.6 I/O B Ref sel 1 9 9 131
Selection of ref source when
control place is I/O B. See
above.
NOTE: I/O B control place can
only be forced active with dig-
ital input (P3.5.1.7).