vacon • 75 Parameters
6
P3.3.1.7 Keypad Ref Sel 1 9 2 121
Selection of ref source when
control place is keypad:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P3.3.1.8 Keypad Reference 0.00 P3.3.1.2 Hz 0.00 184
The frequency reference can
be adjusted on the keypad
with this parameter.
P3.3.1.9 Keypad Direction 0 1 0 123
Motor rotation when control
place is keypad
0 = Forward
1 = Reverse
P3.3.1.10 Fieldbus Ref Sel 1 9 3 122
Selection of ref source when
control place is Fieldbus:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
Table 51. Frequency reference parameters
Code Parameter Min Max Unit Default ID Description