4.3.3 Parameters
Through this submenu, you can reach the application parameter groups and parameters. More
information on parameters in chapter 6.
4.3.4 Diagnostics
Under this menu, you can find
Active faults, Reset faults, Fault history, Counters and Software
info.
4.3.4.1 Active faults
4.3.4.2 Reset faults
4.3.4.3 Fault history
Table 9.
Menu Function Note
Active faults When a fault/faults appear(s), the
display with the name of the fault
starts to blink. Press OK to return
to the Diagnostics menu. The
Active faults submenu shows the
number of faults. Select the fault
and push OK to see the fault-time
data.
The fault remains active until it is
cleared with the Reset button (push
for 2 s) or with a reset signal from the
I/O terminal or fieldbus or by choos-
ing Reset faults (see below).
The memory of active faults can
store the maximum of 10 faults in
the order of appearance.
Table 10.
Menu Function Note
Reset faults In this menu you can reset faults.
For closer instructions, see chap-
ter 7.
CAUTION! Remove external Control
signal before resetting the fault to
prevent unintentional restart of the
drive.
Table 11.
Menu Function Note
Fault history 40 latest faults are stored in the
Fault history.
Entering the Fault history and click-
ing OK on the selected fault shows
the fault time data (details).