vacon • 137 Parameters
6
6.2.13 Prohibit Freq
P3.7.1 R
ANGE 1 LOW LIM
P3.7.2 RANGE 1 HIGH LIM
P3.7.3 RANGE 2 LOW LIM
P3.7.4 RANGE 2 HIGH LIM
P3.7.5 RANGE 3 LOW LIM
P3.7.6 RANGE 3 HIGH LIM
Figure 42. Prohibited frequencies
P3.7.7 RAMPTIMEFACTOR
The Ramp time factor defines the acceleration/deceleration time when the output frequency
is in a prohibited frequency range. The
Ramp time factor is multiplied with the value of param-
eters P3.4.1.2/P3.4.1.3 (
Ramp acceleration/deceleration time). For example the value 0.1
makes the acceleration/deceleration time ten times shorter.
Figure 43. Ramp time factor
Actual Reference
Requested Reference
Low Lim High Lim
Low Lim
High Lim
9118.emf
[s]
[Hz]
Time
Output Frequency
Low Lim
High Lim
Ramp Time
Factor = 2.5
Ramp Time
Factor = 0.3
9211.emf