vacon • 67 Parameters
6
6.1.1 Column explanations
Code = Location indication on the keypad; Shows the operator the parameter num-
ber.
Parameter= Name of parameter
Min = Minimum value of parameter
Max = Maximum value of parameter
Unit = Unit of parameter value; Given if available
Default = Value preset by factory
ID = ID number of the parameter
Description= Short description of parameter values or its function
= More information on this parameter available; Click the parameter name
6.1.2 Group 3.1: Motor settings
6.1.2.1 Group 3.1.1: Motor nameplate
6.1.2.2 Group 3.1.2: Motor Control
Table 45. Motor nameplate parameters
Code Parameter Min Max Unit Default ID Description
P3.1.1.1 Motor Nom Voltg Varies Varies V Varies 110
Find this value U
n
on the
rating plate of the motor.
Note also used connection
(Delta/Star).
P3.1.1.2 Motor Nom Freq 8.00 320.00 Hz Varies 111
Find this value f
n
on the rat-
ing plate of the motor.
P3.1.1.3 Motor Nom Speed 24 19200 rpm Varies 112
Find this value n
n
on the rat-
ing plate of the motor.
P3.1.1.4 Motor Nom Currnt Varies Varies A Varies 113
Find this value I
n
on the rat-
ing plate of the motor.
P3.1.1.5 Motor Cos Phi 0.30 1.00 0.74 120
Find this value on the rating
plate of the motor
P3.1.1.6 Motor Nom Power Varies Varies kW Varies 116
Find this value In on the rat-
ing plate of the motor.
Table 46. Motor control
Code Parameter Min Max Unit Default ID Description
P3.1.2.1 Control mode 0 1 0 600
0 = U/f Freq ctrl open loop
1 = Speed control open loop
P3.1.2.2 Motor type 0 1 0 650
0 = Induction motor
1 = PM motor