Parameters vacon • 108
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.15 Group 3.14: ExtPID Controller
6.1.15.1 Group 3.14.1: Basic settings
For more detailed information, see chapter 6.1.14.
P3.13.9.10 PID setpoint Reduct. 0.0 100.0 % 10.0 1694
Defines the rate of the PID
controller setpoint reduc-
tion when the Input pres-
sure supervision alarm is
active.
V3.13.9.11 InputPress. Monitor Varies Varies Varies Varies 1695
Monitoring value for
selected Input pressure
supervision signal.
Scaling value according to
P3.13.9.4.
Table 100. Basic settings for external PID-controller
Code Parameter Min Max Unit Default ID Description
P3.14.1.1 Enable ExtPID 0 1 0 1630
0 = Disabled
1 = Enabled
P3.14.1.2 Start signal
DigIN
Slot0.2
1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no
effect if PID2 controller is not
enabled in the Basic menu
for PID2
P3.14.1.3 Output in Stop 0.0 100.0 % 0.0 1100
The output value of the PID
controller in % of its maxi-
mum output value while it is
stopped from digital input
P3.14.1.4 Gain 0.00 1000.00 % 100.00 1631
P3.14.1.5 Integration Time 0.00 600.00 s 1.00 1632
P3.14.1.6 Derivation Time 0.00 100.00 s 0.00 1633
P3.14.1.7 ProcessUnitSel. 0 37 0 1635
P3.14.1.8 ProcessUnitMin Varies Varies Varies 0 1664
P3.14.1.9 ProcessUnitMax Varies Varies Varies 100 1665
P3.14.1.10 ProcessUnitDeci 0 4 2 1666
P3.14.1.11 Error inversion 0 1 0 1636
P3.14.1.12 Dead Band Varies Varies Varies 0.0 1637
P3.14.1.13 Dead Band Delay 0.00 320.00 s 0.00 1638
Table 99. Input pressure supervision parameters
Code Parameter Min Max Unit Default ID Description