vacon • 107 Parameters
6
Table 99. Input pressure supervision parameters
Code Parameter Min Max Unit Default ID Description
P3.13.9.1 Superv. Enable 0 1 0 1685
0 = Disabled
1 = Enabled
Enables the Input Pressure
Supervision.
P3.13.9.2 Superv. Signal 0 13 Hz 0 1686
The source of input pres-
sure measurement signal:
0=Analogue input 1
1=Analogue input 2
2=Analogue input 3
3=Analogue input 4
4=Analogue input 5
5=Analogue input 6
6=ProcessDataIn1 (0-100%)
7=ProcessDataIn2 (0-100%)
8=ProcessDataIn3 (0-100%)
9=ProcessDataIn4 (0-100%)
10=ProcessDataIn5 (0-
100%)
11=ProcessDataIn6 (0-
100%)
12=ProcessDataIn7 (0-
100%)
13=ProcessDataIn8 (0-
100%)
P3.13.9.3 Superv. Unit Sel. 0 8 Varies 2 1687
Select unit for supervision.
The supervision signal
(P3.13.9.2) can be scaled to
process units on the panel.
P3.13.9.4 Superv. Unit Decimal 0 4 2 1688
Choose how many deci-
mals to show.
P3.13.9.5 Superv. Unit Min Varies Varies Varies Varies 1689 Unit min and max parame-
ters are the signal values
corresponding to e.g. 4mA
and 20mA respectively
(scaled linearly between
these).
P3.13.9.6 Superv. Unit Max Varies Varies Varies Varies 1690
P3.13.9.7 Superv. Alarm Level Varies Varies Varies Varies 1691
Alarm (Fault ID 1363) will
be launched if supervision
signal stays below the
alarm level longer than the
time defined by parameter
P3.13.9.9.
P3.13.9.8 Superv. Fault Level Varies Varies Varies Varies 1692
Fault (Fault ID 1409) will be
launched if supervision sig-
nal stays below the fault
level longer than the time
defined by parameter
P3.13.9.9.
P3.13.9.9 Superv. Fault Delay 0.00 60.00 s 5.00 1693
Delay time to launch the
Input pressure super-
vision alarm
or fault if
the supervision signal stays
below the alarm/fault level
longer than defined by this
parameter.