EasyManua.ls Logo

Vacon 100X series - Preset Freqs

Vacon 100X series
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
vacon • 125 Parameters
6
6.2.5 Preset Freqs
P3.3.3.1 P
RESETFREQMODE
You can use the preset frequency parameters to define certain frequency references in ad-
vance. These references are then applied by activating/inactivating digital inputs connected to
parameters P3.3.3.10, P3.3.3.11 and P3.3.3.12 (
Preset Freq Sel0, Preset Freq Sel1 and Preset
Freq Sel2
). Two different logics can be selected:
P3.3.3.2
TO
P3.3.3.9 PRESET FREQ 0 TO 7
Value ‘0’ selected for parameter P3.3.3.1:
Preset frequency 0 can be chosen as reference by selecting value 1 for parameter P3.3.1.5.
Other preset frequencies 1 to 7 are selected as reference by dedicating digital inputs for pa-
rameters P3.3.3.10, P3.3.3.11 and/or P3.3.3.12. Combinations of active digital inputs determine
the used preset frequency according to Table 121 below.
The values of the preset frequencies are automatically limited between the minimum and max-
imum frequencies (P3.3.1.1 and P3.3.1.2). See table below.
Preset Freq 0:
Preset frequencies 1 to 7:
Table 119.
Selection
number
Selection name Note
0 Binary coded Combine activated inputs according to Table 121 to choose the
Preset frequency needed.
1 Number (of inputs
used)
According to how many of the inputs assigned for Preset fre-
quency selections are active you can apply the Preset fre-
quencies 1 to 3.
Table 120.
Required action Activated frequency
Choose value 1 for parameter
P3.3.1.5
Preset Freq 0
Table 121. Selection of preset frequencies; = input activated
Activate digital input for
parameter
Activated frequency
P3.3.3.12 P3.3.3.11 P3.3.3.10 Preset Freq 1
P3.3.3.12
P3.3.3.11 P3.3.3.10 Preset Freq 2
P3.3.3.12 P3.3.3.11 P3.3.3.10 Preset Freq 3
P3.3.3.12 P3.3.3.11 P3.3.3.10 Preset Freq 4
P3.3.3.12 P3.3.3.11 P3.3.3.10 Preset Freq 5
P3.3.3.12 P3.3.3.11 P3.3.3.10 Preset Freq 6
P3.3.3.12 P3.3.3.11 P3.3.3.10 Preset Freq 7

Table of Contents

Related product manuals