Parameters vacon • 76
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.4.2 Group 3.3.3: Preset Freqs
Table 52. Preset frequencies parameters
Code Parameter Min Max Unit Default ID Description
P3.3.3.1 PresetFreqMode 0 1 0 182
0 = Binary coded
1 = Number of inputs. Preset
frequency is selected according
to how many of preset speed
digital inputs are active
P3.3.3.2 Preset Freq 0 P3.3.1.1 P3.3.1.2 Hz 5.00 180
Basic preset frequency 0 when
selected by Control reference
parameter (P3.3.1.5).
P3.3.3.3 Preset Freq 1 P3.3.1.1 P3.3.1.2 Hz 10.00 105
Select with digital input:
Preset frequency selection 0
(P3.3.3.10)
P3.3.3.4 Preset Freq 2 P3.3.1.1 P3.3.1.2 Hz 15.00 106
Select with digital input:
Preset frequency selection 1
(P3.3.3.11)
P3.3.3.5 Preset Freq 3 P3.3.1.1 P3.3.1.2 Hz 20.00 126
Select with digital inputs: Preset
frequency selection 0 & 1
P3.3.3.6 Preset Freq 4 P3.3.1.1 P3.3.1.2 Hz 25.00 127
Select with digital input:
Preset frequency selection 2
(P3.3.3.12)
P3.3.3.7 Preset Freq 5 P3.3.1.1 P3.3.1.2 Hz 30.00 128
Select with digital inputs: Preset
frequency selection 0 & 2
P3.3.3.8 Preset Freq 6 P3.3.1.1 P3.3.1.2 Hz 40.00 129
Select with digital inputs: Preset
frequency selection 1 & 2
P3.3.3.9 Preset Freq 7 P3.3.1.1 P3.3.1.2 Hz 50.00 130
Select with digital inputs: Preset
frequency selection 0 & 1 & 2
P3.3.3.10 Preset Freq Sel0
DigIN
SlotA.4
419
Binary selector for Preset
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.
P3.3.3.11 Preset Freq Sel1
DigIN
SlotA.5
420
Binary selector for Preset
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.
P3.3.3.12 Preset Freq Sel2
DigIN
Slot0.1
421
Binary selector for Preset
speeds (0-7). See parameters
P3.3.3.2 to P3.3.3.9.