vacon • 61 Monitoring Menu
5.1.5 Extras & advanced
Table 37. Advanced values monitoring
Code Monitoring value Unit Scale ID Description
V2.6.1 DriveStatusWord 1 43
Bit coded word
B1=Ready
B2=Run
B3=Fault
B6=RunEnable
B7=AlarmActive
B10=DC Current in stop
B11=DC Brake Active
B12=RunRequest
B13=MotorRegulatorActive
V2.6.2 Ready status 1 78
Bit coded information about ready criteria.
Useful for debugging when the drive is not in
ready status.
Values are visible as checkboxes on graphi-
cal keypad. If checked (), the value is
active.
B0: RunEnable high
B1: No fault active
B2: Charge switch closed
B3: DC voltage within limits
B4: Power manager initialized
B5: Power unit is not blocking start
B6: System software is not blocking start
V2.6.3 Appl.StatusWord1 1 89
Bit coded statuses of application.
Values are visible as checkboxes on graphi-
cal keypad. If checked (), the value is
active.
B0=Interlock 1
B1=Interlock 2
B2=Reserved
B3=Ramp 2 active
B4=Mechanical brake control
B5=I/O A control active
B6=I/O B control active
B7=Fieldbus Control Active
B8=Local control active
B9=PC control active
B10=Preset frequencies active
B11=Inching active
B12=Fire Mode active
B13=Motor Preheat active
B14=Forced stop active
B15=Drive stopped from keypad
V2.6.4 Appl.StatusWord2 1 90
Bit coded status of application.
Values are visible as checkboxes on graphi-
cal keypad. If checked (), the value is
active.
B0=Acc/Dec prohibited
B1=Motor switch open
B5=Jockey pump active
B6=Priming pump active
B7=Input pressure supervision (Alarm/Fault)
B8=Frost protection (Alarm/Fault)
B9=Autocleaning active