vacon • 109 Parameters
6
6.1.15.2 Group 3.14.2: Setpoints
Table 101. External PID-controller, setpoints
Code Parameter Min Max Unit Default ID Description
P3.14.2.1 Keypad SP 1 0.00 100.00 Varies 0.00 1640
P3.14.2.2 Keypad SP 2 0.00 100.00 Varies 0.00 1641
P3.14.2.3 Ramp Time 0.00 300.00 s 0.00 1642
P3.14.2.4 Setpoint Selection Varies Varies
DigIN
Slot0.1
1048
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.14.2.5 SP 1 Source 0 22 1 1643
0 = Not Used
1 = Keypad Setpoint 1
2 = Keypad Setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 =ProcessDataIn1
10 =ProcessDataIn2
11 =ProcessDataIn3
12 =ProcessDataIn4
13 =ProcessDataIn5
14 =ProcessDataIn6
15 =ProcessDataIn7
16 =ProcessDataIn8
17 = Temperature Input 1
18 = Temperature Input 2
19 = Temperature Input 3
20 = Temperature Input 4
21 = Temperature Input 5
22 = Temperature Input 6
AI’s and ProcessDataIn are
handled as percent (0.00-
100.00%) and scaled accord-
ing to Setpoint minimum and
maximum. NOTE: Process-
DataIn signals use 2 deci-
mals.
P3.14.2.6 SP 1 Minimum -200.00 200.00 % 0.00 1644
Minimum value at analogue
signal minimum.
P3.14.2.7 SP 1 Maximum -200.00 200.00 % 100.00 1645
Maximum value at analogue
signal maximum.
P3.14.2.8 SP 2 Source 0 22 0 1646 See P3.14.2.5.
P3.14.2.9 SP 2 Minimum -200.00 200.00 % 0.00 1647
Minimum value at analogue
signal minimum.
P3.14.2.10 SP 2 Maximum -200.00 200.00 % 100.00 1648
Maximum value at analogue
signal maximum.