Parameters vacon • 110
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.15.3 Group 3.14.3: Feedbacks
For more detailed information, see chapter 6.1.14.
6.1.15.4 Group 3.14.4: Feedback Superv.
For more detailed information, see chapter 6.1.14.
Table 102. External PID-controller, feedbacks
Code Parameter Min Max Unit Default ID Description
P3.14.3.1 Function 1 9 1 1650
P3.14.3.2 Gain -1000.0 1000.0 % 100.0 1651
P3.14.3.3 FB 1 Source 0 25 1 1652 See P3.13.3.3.
P3.14.3.4 FB 1 Minimum -200.00 200.00 % 0.00 1653
Minimum value at analogue
signal minimum.
P3.14.3.5 FB 1 Maximum -200.00 200.00 % 100.00 1654
Maximum value at analogue
signal maximum.
P3.14.3.6 FB 2 Source 0 25 2 1655 See P3.13.3.6.
P3.14.3.7 FB 2 Minimum -200.00 200.00 % 0.00 1656
Minimum value at analogue
signal minimum.
P3.14.3.8 FB 2 Maximum -200.00 200.00 % 100.00 1657
Maximum value at analogue
signal maximum.
Table 103. External PID-controller, process supervision
Code Parameter Min Max Unit Default ID Description
P3.14.4.1 Enable Superv 0 1 0 1659
0 = Disabled
1 = Enabled
P3.14.4.2 Upper limit Varies Varies Varies Varies 1660
P3.14.4.3 Lower limit Varies Varies Varies Varies 1661
P3.14.4.4 Delay 0 30000 s 0 1662
If the desired value is not
reached within this time a
fault or alarm is activated.
P3.14.4.5 Supervision Fault 0 3 2 757 See P3.9.1.2