vacon • 73 Parameters
6
P3.2.10 Rem to Loc Funct 0 2 2 181
Choose whether to copy the
Run state and Reference
when changing from
Remote to Local (keypad)
control:
0 = Keep Run
1 = Keep Run & Reference
2 = Stop
P3.2.11 Start Analogue Signal 0 1 0 1810
0= AI1
1= AI2
P3.2.12 Start Analogue Level 0.00 100.00 % 10.00 1857
Start is set below this level
(unscaled signal). Start-
stop logic is reversed if >
P3.2.13
P3.2.13 Stop Analogue Level 0.00 100.00 % 80.00 1856
Start is set above this level
(unscaled signal). Start-
stop logic is reversed if <
P3.2.12
Table 50. Start/Stop Setup menu
Code Parameter Min Max Unit Default ID Description