Parameters vacon • 84
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.6.5 Expander slots D and E digital outputs
Shows only parameters for existing outputs on option boards placed in slots D and E. Selec-
tions as in Standard RO1 (P3.5.3.2.1).
This group or these parameters are not visible if no digital outputs exist in slots D or E.
6.1.6.6 Group 3.5.4: Analogue outputs
Group 3.5.4.1: Slot A Basic
M3.5.3.2.5 Basic R02 ON delay 0.00 320.00 s 0.00
1100
5
See M3.5.3.2.2.
M3.5.3.2.6 Basic R02 OFF delay 0.00 320.00 s 0.00
1100
6
See M3.5.3.2.3.
Table 67. Standard I/O board analogue output settings
Code Parameter Min Max Unit Default ID Description
P3.5.4.1.1 AO1 function 0 19 2 10050
0=TEST 0% (Not used)
1=TEST 100%
2=Output freq (0 -fmax)
3=Freq reference (0-fmax)
4=Motor speed (0 - Motor
nominal speed)
5=Output current (0-I
nMotor
)
6=Motor torque (0-T
nMotor
)
7=Motor power (0-P
nMotor
)
8=Motor voltage (0-U
nMotor
)
9=DC link voltage (0-1000V)
10=PID1 output (0-100%)
11=Ext.PID output (0-100%)
12=ProcessDataIn1 (0-100%)
13=ProcessDataIn2 (0-100%)
14=ProcessDataIn3 (0-100%)
15=ProcessDataIn4 (0-100%)
16=ProcessDataIn5 (0-100%)
17=ProcessDataIn6 (0-100%)
18=ProcessDataIn7 (0-100%)
19=ProcessDataIn8 (0-100%)
P3.5.4.1.2 AO1 filter time 0.0 300.0 s 1.0 10051
Filtering time of analogue out-
put signal. See P3.5.2.1.2
0 = No filtering
P3.5.4.1.3 AO1 minimum 0 1 0 10052
0 = 0 mA / 0V
1 = 4 mA / 2V
Signal type (current/voltage)
selected with dip switches.
Note the difference in ana-
logue output scaling in param-
eter P3.5.4.1.4.
See also parameter P3.5.2.1.3.
P3.5.4.1.4 AO1 minimum scale Varies Varies Varies 0.0 10053
Min scale in process unit
(depends on selection of AO1
function).
P3.5.4.1.5 AO1 maximum scale Varies Varies Varies 0.0 10054
Max scale in process unit
(depends on selection of AO1
function)
Table 66. Digital output settings on standard I/O board
Code Parameter Min Max Unit Default ID Description