Fault vacon • 162
Service support: find your nearest Vacon service center at www.vacon.com
7
11 100
Output phase
supervision
Current measurement has detected
that there is no current in one motor
phase.
Check motor cable and motor.
12
110
Brake chopper
supervision
(hardware fault)
No brake resistor installed.
Brake resistor is broken.
Brake chopper failure.
Check brake resistor and
cabling.
If these are ok, the chopper is
faulty. Contact the distributor
near to you.
111
Brake chopper
saturation alarm
13 120
AC drive under-
temperature
(fault)
Too low temperature measured in
power unit’s heatsink or board. Heat-
sink temperature is under -10°C.
Check the ambient tempera-
ture
14
130
AC drive over-
temperature
(fault, heatsink)
Too high temperature measured in
power unit’s heatsink or board. Heat-
sink temperature is over 100°C.
Check the correct amount and
flow of cooling air.
Check the heatsink for dust.
Check the ambient tempera-
ture.
Make sure that the switching
frequency is not too high in
relation to ambient tempera-
ture and motor load.
131
AC drive over-
temperature
(alarm, heatsink)
132
AC drive over-
temperature
(fault, board)
133
AC drive over-
temperature
(alarm, board)
15 140
Motor stalled Motor is stalled. Check motor and load.
16 150
Motor overtem-
perature
Motor is overloaded.
Decrease motor load.
If no motor overload exists,
check the temperature model
parameters.
17 160
Motor underload Motor is underloaded. Check load.
19
180
Power overload
(short-time
supervision)
Drive power is too high. Decrease load.
181
Power overload
(long-time super-
vision)
25
240
Motor control
fault
Start angle identification has failed.
Reset the fault and restart.
Should the fault re-occur, con-
tact the distributor near to you.
241
Generic motor control fault.
26 250
Start-up pre-
vented
Start-up of the drive has been pre-
vented. Run request is ON when a new
software (firmware or application),
parameter setting or any other file,
which has affects the operation of the
drive, has been loaded to drive.
Reset the fault and stop the AC
drive.
Load the software and start the
AC drive.
30 530
STO fault
Emergency stop button has been con-
nected or some other STO operation
has been activated.
When the STO function is acti-
vated, the drive is in safe state.
32 312
Fan cooling Fan life time is up.
Change fan and reset fan life
time counter.
Fault
code
Fault
ID
Fault name Possible cause Remedy
Table 125. Fault codes and descriptions.