3
vacon • 19 Startup
P1.34.7 SP 1 Sleep Freq 0.00 320.00 Hz 0.00 1016
Drive goes to sleep mode
when the output frequency
stays below this limit for a
time greater than that
defined by parameter Sleep
delay.
P1.34.8 SP 1 Sleep Delay 0 3000 s 0 1017
The minimum amount of
time the frequency has to
remain below the Sleep level
before the drive is stopped.
P1.34.9 SP 1 WakeUpLevel Varies 0.00 1018
Defines the level for the PID
feedback value wake-up
supervision. Uses selected
process units.
P1.34.10 Preset Freq 1 P1.3 P1.4 Hz 10.0 105 Preset Freq 1
Table 5. PID Control start-up wizard menu