vacon • 69 Parameters
6
6.1.2.3 Group 3.1.3: Limits
6.1.2.4 Group 3.1.4: Open loop
P3.1.2.11 Under Volt. Control 0 1 1 608
0 = Disabled
1 = Enabled
P3.1.2.12 Energy optimization 0 1 0 666
The drive searches for the
minimum motor current in
order to save energy and to
lower the motor noise. This
function can be used e.g. in
fan and pump applications
0 = Disabled
1 = Enabled
P3.1.2.13 StatorVoltAdjust 50.0 150.0 % 100.0 659
Parameter for adjusting the
stator voltage in permanent
magnet motors.
P3.1.2.14 Overmodulation 0 1 1
Maximizes drive output volt-
age, but increases motor
current harmonics.
0= Disabled
1= Enabled
Table 47. Motor limit settings
Code Parameter Min Max Unit Default ID Description
P3.1.3.1 Current limit Varies Varies A Varies 107
Maximum motor current
from AC drive
P3.1.3.2 MotorTorqueLimit 0.0 300.0 % 300.0 1287
Maximum motoring side
torque limit
P3.1.3.3 GenerTorqueLimit 0.0 300.0 % 300.0 1288
Maximum generating side
torque limit
P3.1.3.4 MotorPowerLimit 0.0 300.0 % 300.0 1290
Maximum motoring side
power limit
P3.1.3.5 GenerPowerLimit 0.0 300.0 % 300.0 1289
Maximum generating side
power limit
Table 48. Open loop settings
Code Parameter Min Max Unit Default ID Description
P3.1.4.1 U/f ratio 0 2 0 108
Type of U/f curve between
zero frequency and the field
weakening point.
0=Linear
1=Squared
2=Programmable
P3.1.4.2 Field WeakngPnt 8.00 P3.3.1.2 Hz Varies 602
The field weakening point is
the output frequency at
which the output voltage
reaches the field weakening
point voltage
Table 46. Motor control