vacon • 93 Parameters
6
6.1.10.7 Group 3.9.8: AI Low Protection
6.1.10.8 Group 3.9.9: User Defined Fault 1
6.1.10.9 Group 3.9.10: User Defined Fault 2
Table 78. AI Low Protection settings
Code Parameter Min Max Unit Default ID Description
P3.9.8.1 AI Low Protection 0 2 2 767
This parameter defines if the
AI Low protection is enabled
or disabled.
0 = Disabled
1 = Enabled in Run State
2 = Enabled in Run&Stop
States
P3.9.8.2 AI Low Fault 0 5 0 700
Response when an analogue
signal in use goes below 50%
of the minimum signal range.
0 = No action
1 = Alarm
2 = Alarm, Preset Freq
3 = Alarm, Previous Freq
4= Fault (Stop according to
stop mode)
5 = Fault (Stop by coasting)
Table 79. User Defined Fault 1 settings
Code Parameter Min Max Unit Default ID Description
P3.9.9.1 User Defined Fault 1
DigIN
Slot0.1
1552
3
Digital input selection for
activating User Defined Fault
(1 or 2)
P3.9.9.2 UserDef. Fault1 Resp. 0 3 3
1552
5
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
Table 80. User Defined Fault 2 settings
Code Parameter Min Max Unit Default ID Description
P3.9.10.1 User Defined Fault 2
DigIN
Slot0.1
1552
4
Digital input selection for
activating User Defined Fault
(1 or 2)
P3.9.10.2 UserDef. Fault2 Resp. 0 3 3
1552
6
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)