In the menu [Temperature control], select the menu line
[Diff. temp. control] with the touchwheel.
You will see the following submenu [Difference temperature control]
with all setting values:
Limit value
D-temp COOLER
The "D-temp COOLER" limit value specifies by how many degree the outside
temperature must be lower than the inside temperature for the window to
open.
If the difference between outside and inside temperature becomes greater
than this value, the window is opened.
Example Your max. comfort temperature is, for example, 26 °C and it has already
been reached. If the outside temperature is lower than the inside temperature
of the set difference temperature "D-temp COOLER", the window is opened
for venting and cooling. If you set 5 °C here, the window is only opened
again when the outside temperature 26 °C - 5 °C = 21 °C is fallen below.
The setting range is 0...25 °C.
Turn the touchwheel to set the limit value "D-temp COOLER".
The function button [---] sets the value to [---] (deactivated); the function
button [Stand.] sets the limit value "D-temp. COOLER" to 5 °C (factory set-
ting).