EasyManua.ls Logo

Watlow ez-zone pm - Page 140

Watlow ez-zone pm
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow EZ-ZONE
®
PMI Controller 136 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
t.For
t.For
Timer (1)
Time Format
Select the time for-
mat.
tЛЏS Time
Minutes:Seconds
(1943)
thЛЏ Time
Hours:Minutes
(1944)
Time
Minutes:
Seconds
Instance 1
Map 1 Map 2
4616 8546
0x83
(131)
1
0x18
(24)
- - - - 31024 uint
RWES
hoUr
hoUr
Timer (1)
Hours
Set the timer period
hours.
0 to 99 0 Instance 1
Map 1 Map 2
4618 8548
0x83
(131)
1
0x19
(25)
- - - - 31025 uint
RWES
ЛЏin
Min
Timer (1)
Minutes
Set the timer period
minutes.
0 to 59 0 Instance 1
Map 1 Map 2
4620 8550
0x83
(131)
1
0x1A
(26)
- - - - 31026 uint
RWES
SEC
SEC
Timer (1)
Seconds
Set the timer period
seconds.
0 to 59 10 Instance 1
Map 1 Map 2
4622 8552
0x83
(131)
1
0x1B
(27)
- - - - 31027 uint
RWES
Ct.SP
Ct.SP
Timer (1)
Closed Loop Timer
Set Point
Set the set point
that will be in ef-
fect during the
timer period.
-1999.000 to
9999.000°F or units
-1110.555 to
5555.000°C
75 Instance 1
Map 1 Map 2
4624 8554
0x83
(131)
1
0x1C
(28)
- - - - 31028 float
RWES
St
St
Timer (1)
Signal Time
Set the period of
time that a signal
output to be ac-
tivated after the
timer period is com-
plete. Assign a digi-
tal output for this
function in Timer
Event Output 3.
1 to 3600 Seconds 1 Instance 1
Map 1 Map 2
4658 8588
0x83
(131)
1
0x2D
(45)
- - - - 31045 uint
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set

Table of Contents

Other manuals for Watlow ez-zone pm

Related product manuals