Watlow EZ-ZONE
®
PMI Controller 116 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
L.it
L.it
Limit (1)
Integrate with Sys-
tem
In a limit state the
controller will turn
off the outputs,
terminate an ac-
tive profile and
freeze PID and
TRU-TUNE+
®
calcu-
lations.
no No (59)
yES Yes (106)
No Instance 1
Map 1 Map 2
694 734
0x70
(112)
1
8
- - - - 12008 uint
RWES
No Dis-
play
Limit (1)
Limit State
Clear limit once
limit condition is
cleared.
off Off (62)
nonE None (61)
Li.h Limit High (51)
Li.L Limit Low (52)
Err Error (28)
- - - -
Instance 1
Map 1 Map 2
690 730
0x70
(112)
1
6
- - - - 12006 uint
R
Loop
sEt
Control Loop Menu
h.ag
h.Ag
Control Loop (1 to
2)
Heat Algorithm
Set the heat con-
trol method.
off Off (62)
pid PID (71)
on.of On-Off (64)
PID
Instance 1
Map 1 Map 2
1884 2364
Instance 2
Map 1 Map 2
1954 2434
0x97
(151)
1 to 2
3
72 8003 uint
RWES
C.ag
C.Ag
Control Loop (1 to
2)
Cool Algorithm
Set the cool control
method.
off Off (62)
pid PID (71)
on.of On-Off (64)
Off Instance 1
Map 1 Map 2
1886 2366
Instance 2
Map 1 Map 2
1956 2436
0x97
(151)
1 to 2
4
73 8004 uint
RWES
C.Cr
C.Cr
Control Loop (1 to
2)
Cool Output Curve
Select a cool
output curve to
change the re-
sponsiveness of
the system.
off Off (62)
Cr.a Non-linear Curve
1 (214)
Cr.b Non-linear Curve
2 (215)
Off
Instance 1
Map 1 Map 2
1888 2368
Instance 2
Map 1 Map 2
1958 2438
0x97
(151)
1 to 2
5
- - - - 8038 uint
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set