Watlow EZ-ZONE
®
PMI Controller 149 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
J1939 CAN bus (Digital Input Bus)
J.ad
J.Ad
Communications (2)
J1939 Device Ad-
dress
Set the Device ad-
dress.
0 to 255
249 - - - - - - - - - - - - 94001 un-
signed
8-bits
RWE
J.bAU
J.bAu
Communications (2)
J1939 Baud Rate
Set the Digital Input
Bus communications
speed.
125 125 kb (1351)
250 250 kb (1352)
500 500 kb (1353)
1000 1000 kb
(1364)
250 - - - - - - - - - - - - 94002 uint
RWE
d.En
d.En
Communications (2)
J1939 Device En-
able
Enables the device
for communication.
no No (59)
yES Yes (106)
Yes - - - - - - - - - - - - 94003 uint
RWE
tEds
tEds
Communications (2)
Transducer Elec-
tronic Data Sheet
Contains sensor
technical character-
istics when manu-
factured.
no No (59)
yES Yes (106)
Yes - - - - - - - - - - - - 94004 float
R
C_F
C_F
Communications (2)
J1939 Display Units
Select which scale
to use for tempera-
ture passed over
communications
port 2.
C °C (15)
F °F (30)
nonE None (61)
°C - - - - - - - - - - - - 17050 uint
RWE
ЛЏap
Map
Communications (2)
Data Map
If set to 1 the con-
trol will use legacy
Modbus mapping. If
set to 2, the control
will use new Modbus
mapping to accommo-
date new functions.
Not used with J1939.
1 to 2 1 - - - - - - - - - - - - 17059 uint
RWE
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set