Watlow EZ-ZONE
®
PMI Controller • 57 • Chapter 4 Home Page
Chapter 4: Home Page
4
Default Home Page Parameters
Watlow's patented user-dened menu system improves operational efciency. The user-
dened Home Page provides you with a shortcut to monitor or change the parameter values
that you use most often. The default Home Page is shown on the following page. When a pa-
rameter normally located in the Setup Page or Operations Page is placed in the Home Page,
it is accessible through both. If you change a parameter in the Home Page, it is automatically
changed in its original page. If you change a parameter in its original page it is automatically
changed in the Home Page. Use the Advance Key ‰
to step through the other parameters.
When not in pairs, the parameter prompt will appear in the lower display, and the parameter
value will appear in the upper display. You can use the Up ¿ and Down ¯ keys to change the
value of writable parameters, just as you would in any other menu.
Note:
If a writable value is placed on the upper display and is paired with another read only
parameter on the lower display, the arrow keys affect the setting of the upper display. If
two writable parameters are paired, the arrow keys affect the lower display.
• The Attention attn parameter appears only if there is an active message. An example of
an active message could be a Current Error C.Er1, or it could be for information only like
Autotune
tU n1
taking place.
• If Control Mode is set to Auto, the Process Value is in the upper display and the Set Point
(read-write) is in the lower display.
• If a profile is running, the process value is in the upper display and the Target Set Point
(read only) is in the lower display. If Control Mode is set to Manual, the Process Value is in
the upper display and the output power level (read-write) is in the lower display.
• If Control Mode is set to Off, the Process Value is in the upper display and off (read only)
is in the lower display.
• If a sensor failure has occurred, dashes
----
will be displayed in the upper display and
the Manual Power (read-write) is in the lower display.