Watlow EZ-ZONE
®
PMI Controller 72 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
Err
Err
Digital Bus (1 to 6)
Output Error
nonE None (61)
OpEn Open (65)
shrt Shorted (127)
E.ЛЏ Measurement
Error (140)
E.CaL Bad Calibra-
tion Data (139)
Er.ab Ambient Er-
ror (9)
E.rtd RTD Error
(141)
faiL Fail (32)
Er.ЛЏ. Math Error
(1423)
nsrc Not Sourced
(246)
StAL Stale (883)
Stale - - - - - - - - - - - - 95004 float
R
Lnr
opEr
Linearization Menu
Su.a
Su.A
Linearization (1 to
2)
Source Value A
View the value of
Source A.
Source A of Linear-
ization 1 is con-
nected to Analog
Input 1, Source A of
Linearization 2 is
connected to Analog
Input 2
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3566
Instance 2
Map 1 Map 2
- - - - 3636
0x86
(134)
1 to 2
4
- - - -
34004 float
R
ofst
oFSt
Linearization (1 to
2)
Offset
Set an offset to
be applied to this
function's output.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0 Instance 1
Map 1 Map 2
- - - - 3570
Instance 2
Map 1 Map 2
- - - - 3640
0x86
(134)
1 to 2
6
- - - -
34006 float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set