Watlow EZ-ZONE
®
PMI Controller 108 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
b.pr
b.Pr
Process Value (1 to
2)
Barometric Pres-
sure***
If Process Value
function is set for
Wet Bulb / Dry
Bulb, define pres-
sure value used for
humidity calcula-
tion.
10.0 to 16.0 14.7 Instance 1
Map 1 Map 2
- - - - 3338
Instance 2
Map 1 Map 2
- - - - 3408
0x7E
(126)
1 to 2
0x1E
(30)
- - - - 26030 float
RWES
fiL
FiL
Process Value (1 to
2)
Filter
Filtering smooths
out the output sig-
nal of this function
block. Increase the
time to increase
filtering.
0.0 to 60.0 seconds 0.0 Instance 1
Map 1 Map 2
- - - - 3330
Instance 2
Map 1 Map 2
- - - - 3400
0x7E
(126)
1 to 2
0x1A
(26)
- - - - 26026 float
RWES
*** Pressure Altitude calculation is based on the International Standard Atmosphere 1976
dio
sEt
Digital Input/Output Menu
dir
dir
Digital Input/Output
(5 to 12)
Direction
Set this function to
operate as an input
or output.
Note:
Modbus Map 1
has instances 5
through 8 only
otpt Output (68)
in Input Voltage
(193)
iCon Input Dry Con-
tact (44)
Output Instance 5
Map 1 Map 2
1000 1120
Offset to
next instance
(Map 1
& Map 2)
equals +30
0x6A
(106)
5 to 12
1
82 6001 uint
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.