EasyManua.ls Logo

Watlow ez-zone pm - Global Menu

Watlow ez-zone pm
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow EZ-ZONE
®
PMI Controller 142 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
Fi
Fi
Function Key (1 to
2)
Function Instance
Select which in-
stance the EZ
Key will affect. If
only one instance
is available, any
selection will af-
fect it.
0 to 40 0 Instance 1
Map 1 Map 2
1366 1606
Instance 2
Map 1 Map 2
1386 1626
0x96
(110)
3 to 4
4
139 10004 - - - -
gLbL
SEt
Global Menu
C_F
C_F
Global
Display Units
Select which scale
to use for tempera-
ture.
F °F (30)
C °C (15)
°F Instance 1
Map 1 Map 2
1838 2308
0x67
(103)
1
5
110 3005
uint
RWES
AC.LF
AC.LF
Global
AC Line Frequency
Set the frequency
to the applied ac
line power source.
50 50 Hz (3)
60 60 Hz (4)
60 Hz Instance 1
Map 1 Map 2
886 1006
0x6A
(106)
1
4
89 1034 uint
RWES
r.typ
r.tyP
Global
Ramping Type
ratE Rate (81)
ti Time (143)
Time Instance 1
Map 1 Map 2
- - - - 4414
0x7A
(122)
1
26 (38)
- - - - 22038 uint
RWE
P.typ
P.tyP
Global
Profile Type
Set the profile
startup to be based
on a set point or a
process value.
StPt Set Point (85)
Pro Process (75)
Set Point Instance 1
Map 1 Map 2
2534 4354
0x7A
(122)
1
8
- - - - 22008 uint
RWE
gSE
gSE
Global
Guaranteed Soak
Enable
Enables the guaran-
teed soak deviation
function in profiles.
oFF Off (62)
on On (63)
Off Instance 1
Map 1 Map 2
2530 4350
0x7A
(122)
1
6
- - - - 22006 uint
RWE
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set

Table of Contents