Watlow EZ-ZONE
®
PMI Controller 146 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
Standard Bus
Ad.S
Ad.S
Communications 1
Standard Bus Ad-
dress
Set the network
address of this con-
troller. Each device
on the network
must have a unique
address.
The Zone Display on
the front panel will
display this number.
1 to 16 1 Instance 1
Map 1 Map 2
2480 2960
0x96
(150)
1
1
- - - - 17001 uint
RWE
Modbus RTU
Ad.ЛЏ
Ad.M
Communications (1
or 2)
Modbus Address
Set the network
address of this con-
troller. Each device
on the network
must have a unique
address.
1 to 247 1 Instance 1
Map 1 Map 2
2482 2962
Instance 2
Map 1 Map 2
2500 2980
0x96
(150)
1 to 2
2
- - - - 17007 uint
RWE
bAUd
bAUd
Communications (1
or 2)
Baud Rate
Set the speed of
this controller's
communications to
match the speed of
the
Modbus
serial
network.
9600 9,600 (188)
19.2 19,200 (189)
38.4 38,400 (190)
9,600 Instance 1
Map 1 Map 2
2484 2964
Instance 2
Map 1 Map 2
2504 2984
0x96
(150)
1 to 2
3
- - - - 17002 uint
RWE
PAr
PAr
Communications (1
or 2)
Parity
Set the parity of
this controller to
match the parity of
the
Modbus
serial
network.
nonE None (61)
EuEn Even (191)
odd Odd (192)
None Instance 1
Map 1 Map 2
2486 2966
Instance 2
Map 1 Map 2
2506 2986
0x96
(150)
1 to 2
4
- - - - 17003 uint
RWE
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set