Watlow EZ-ZONE
®
PMI Controller 147 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
C_f
C_F
Communications (1
or 2)
Display Units
Select whether this
communications
channel will display
in Celsius or Fahr-
enheit.
Note:
Applies to Modbus
only.
f Fahrenheit (30)
C Celsius (15)
F Instance 1
Map 1 Map 2
2490 2970
0x96
(150)
1
6
- - - - 17050 uint
RWE
ЛЏ.hL
M.hL
Communications (1
or 2)
Modbus Word Order
Select the word
order of the two
16-bit words in the
floating-point val-
ues.
Lohi Low-High
(1331)
hiLo High-Low
(1330)
Low-High Instance 1
Map 1 Map 2
2488 2968
Instance 2
Map 1 Map 2
2508 2988
0x96
(150)
1 to 2
5
- - - - 17043 uint
RWE
ЛЏap
Map
Communications (1
or 2)
Data Map
If set to 1 the con-
trol will use PM leg-
acy mapping. If set
to 2 the control will
use new mapping to
accommodate new
functions.
1 to 2 1 if 9
th
digit
of part
number
is a D or
1 other-
wise, 2.
- - - - - - - - - - - - 17059 uint
RWE
nU.S
nV.S
Communications (1
or 2)
Non-Volatile Save
If set to Yes all
values written to
the control will be
saved in EEPROM.
The EEPROM allows
for approximately
one million writes.
yEs Yes (106)
no No (59)
Yes Instance 1
Map 1 Map 2
2494 2974
0x96
(150)
1
8
198 17051 uint
RWE
no dis-
play
Communications (1
or 2)
Tick
Value increases at
1mS rate.
0 to 4,294,967,295 - - - - Instance 1
Map 1 Map 2
5020 8950
- - - - - - - - 16006 un-
signed
32-bit
RWE
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set

Table of Contents