Watlow EZ-ZONE
®
PMI Controller • 133 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
a.sir
A.Sir
Alarm (1 to 4)
Silence Alarm
Write to this reg-
ister to silence an
alarm
Note:
If an alarm is
setup to silence
alarm when active
a.sir will appear
on the display.
siL Silence (1010)
- - - - Instance 1
Map 1 Map 2
1506 1906
Offset to
next in-
stance
(Map1 1
equals
+50, Map 2
equals +60)
0x6D
(109)
1 to 4
0xE (14)
- - - - 9014 uint
W
a.st
A.St
Alarm (1 to 4)
Alarm State
Current state of
alarm
str Startup (88)
nonE None (61)
bLo Blocked (12)
aL.L Alarm low (8)
aL.h Alarm high (7)
aL.E Error (28)
- - - - Instance 1
Map 1 Map 2
1496 1896
Offset to
next in-
stance
(Map1 1
equals
+50, Map 2
equals +60)
0x6D
(109)
1 to 4
9
- - - - 9009 uint
R
CUrr
SEt
Current Menu
Note:
For further description and usage tips see the CT Appli-
cation Note in this User's Guide.
C.Sd
C.Sd
Current (1)
Sides
Select which side or
sides will be moni-
tored.
oFF Off (62)
high High (37)
loФІ Low (53)
both Both (13)
off Instance 1
Map 1 Map 2
1128 1368
0x73
(115)
1
5
145 15005 uint
RWES
CU.r
CU.r
Current (1)
Indicate Reading
Use Indicate Reading
to display solid-state
relay (SSR) failure
and heater failure
messages.
no No (59)
yEs Yes (106)
no Instance 1
Map 1 Map 2
1126 1366
0x73
(115)
1
4
146 15004 uint
RWES
C.dt
C.dt
Current (1)
Input Detection
Threshold
For factory adjust-
ment only.
3 to 59 9 Instance 1
Map 1 Map 2
1142 1382
0x73
(115)
1
0xC (12)
147 15012 uint
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set